Points for installing a pressure reducing valve

     

(1) The installation of the pressure reducing valve should be carried out after the pressure test and flushing of the water supply pipe network are qualified, and the pipeline pressure test and flushing records should be checked.

(2) Before the installation of the pressure reducing valve, check that its specifications and models should be consistent with the design, the external control pipeline and the connecting parts of the guide valve should not be loose, the appearance should be without mechanical damage, and the foreign matter in the valve should be cleaned.

(3) For convenient operation and maintenance, the pressure reducing valve is generally installed upright on the horizontal pipeline. The proportional pressure reducing valve should be installed vertically, and when installed horizontally, the orifice of the single breathing hole pressure reducing valve should be downward, and the orifice of the double breathing hole pressure reducing valve should be in a horizontal position; Adjustable pressure reducing valves should be installed horizontally and the bonnet should be up.

(4) The installation of the pressure reducing valve must be in strict accordance with the direction of the arrow on the valve body to keep the same as the direction of fluid flow. If the water quality is not clean and contains some impurities, a filter must be installed at the upstream inlet of the pressure reducing valve (we recommend a filtration accuracy of not less than 0.5mm).

(5) The filter should be installed on the inlet side, and the control valve should be installed before and after it.

(6) In order to prevent overpressure after the valve, a pressure reducing valve should be installed at no less than 4M from the valve outlet. If a pressure reducing valve needs to be installed in a hot water system, you must install a check valve between the pressure reducing valve and the expansion tank. This not only allows the expansion tank to absorb the volume of water increased due to thermal expansion, but also prevents the influence of hot water backflow or pressure fluctuations on the pressure reducing valve, ensuring the normal operation of the pressure reducing valve for a long time. The pressure reducing valve plays a certain check role in the pipeline, in order to prevent the harm of water hammer, a small expansion tank can also be installed to prevent damage to the pipeline and valve, the filter must be installed in front of the inlet pipe of the pressure reducing valve, and the expansion water tank must be installed behind the outlet pipe of the pressure reducing valve.

(7) When installing a pressure reducing valve without its own pressure gauge, the pressure gauge should be installed in the adjacent parts before and after.

Points